Relay Protection Testing Device | DTE 450/3000
Relay Protection Testing Device DTE–450/3000 (hereinafter – device) is intended for
- adjustment and testing of simple relay protection (RPA) in place of their installation at power plants, substations, industrial plants or in the laboratory
- adjustment and testing of electroautomatics elements (electromagnetic relays, contactors, motor starters, etc.)
- adjustment and testing of circuit breakers
The device is implemented within single body, which creates additional convenience during use. It includes connecting wires and cables to connect testing devices.
SKU:
DTE–450/3000E
Category: DTE | Dnipro Energy Technologies
Tags: relay protection, relay protection testing device
Description
Relay Protection Testing Device | DTE 450/3000
Technical specifications
Power supply AC voltage | 220V ± 10% (50Hz) |
Maximum supply consumption current | 50 A |
Maximum power consumption | 5000 W |
Environment temperature | -10°C … +45°C |
Storage temperature | -20°C … +45°C |
Relative air humidity at +25°C | 80% max |
Atmospheric pressure, mm Hg. | 630 – 800 |
Device weight, without connecting wires set, at most | 36 kg |
Continuous operation mode, at least | 120 min |
Average service time | 10 years |
Output voltage
Range of sinusoidal power frequency output voltage, generated by the device is divided into three subranges | 0 –– 50 V 0 –– 250 V 0 –– 450 V |
Range of rectified output voltage, generated by the device is divided into three subranges | 0 –– 50 V 0 –– 250 V 0 –– 450 V |
Output voltage measuring accuracy | 1,5% |
Measurement resolution of the output voltage | 10 mV |
Output current
Range of sinusoidal power frequency output current, generated by the device is divided into two subranges | 0 –– 20 A 0 –– 200 A |
Optionally, there is added the range of the pulse-phase output current of power frequency for testing circuit breakers | 0 –– 3000 A |
Output current measuring accuracy | 1,5 % |
Measurement resolution of the output current | 10 mA |
Additionally
Time intervals measurer in the range 0 | 9999,9 sec. |
Measurement accuracy of time interval | 0,2 ms |
measurement resolution of time interval | 0,1 ms |
Package contents
N | Name | Quantity |
1 | DTE–450/3000 device | 1 pc. |
2 | Test cables set | 1 set |
3 | Device power cord | 1 pc. |
4 | Carrying bag for storaging and transporting of connection cables | 1 pc. |
5 | Current sensor, 3000/5(А) | 1 pc. |
6 | DTE–450/3000 operation manual | 1 pc. |
Reviews (0)
Be the first to review “Relay Protection Testing Device | DTE 450/3000”
Related products
Drying Apparatus for Dielectric Protective Equipment
High Voltage Diode Device
High Voltage Diode Device | DTE 70/50; is intended for testing and certification of high-voltage cables and dielectric insulators on distribution points of electrical networks and transformer substations, as part of mobile electrical laboratory. It can be used in stationary electrophysical laboratories as a high voltage source for solid dielectrics testing.
High Voltage Stationary Stand | DTE 15-4D
High Voltage Stationary Stand | DTE 15-4D; is designed for the following works:
- Tests of dielectric rubber gloves, a bot, electric tools, etc. Variable high voltage industrial frequency, adjustable within 100V – 15kV.
- Checks of neon lamps with variable voltage of industrial frequency, adjustable within 5 – 250V.
High Voltage Test System for Solid Dielectrics Testing
High Voltage Test System for Solid Dielectrics Testing
- Testing the high-voltage cables and the cables sheaths with 6,10,15,20 kW operating voltage and all types insulation such as XLPE and PILC.
- Testing insulators and other electric equipment by high voltage power frequency AC.
- Testing high-voltage switches’ vacuum chambers.
- Laboratory and research works.
Insulation Tester | DTE-6
Relay Protection Testing Device | DTE 450/2000
Сircuit Breaker Testing Device | DTE 20M
Сircuit Breaker Testing Device; is intended for operability testing and ampere-second characteristics monitoring of circuit breakers by power frequency AC in the range 20A – 20kA. It is capable to measure and record time and values of current transmitted through the circuit breaker, hereinafter – CB. It can be used as a controlled power source of AC up to 20kA in low impedance power circuits.
Сircuit Breaker Testing Device | DTE-10M
Сircuit Breaker Testing Device | DTE-10M; is intended for testing and certification of high-voltage cables and dielectric insulators on distribution points of electrical networks and transformer substations, as part of mobile electrical laboratory. It can be used in stationary electrophysical laboratories as a high voltage source for solid dielectrics testing.
Reviews