MTS-10-10K Insulation resistance meter also known as megohmmeter, high voltage insulation resistance tester, etc., for the insulation resistance test. The instrument has a large LCD screen gray backlit display, data storage, data access, alarm, automatic shutdown and other functions. At the same time, it also has the function of measuring AC voltage absorption ratio and polarization index of DC voltage. The machine is beautiful and upscale, has a wide range, high resolution, convenient operation, easy to carry, accurate, reliable, stable performance, strong anti-interference ability.
MTS-10-10K has a shockproof, dustproof, moisture-proof structure and is a commonly used and indispensable instrument for telecommunications, electricity, meteorology, computer rooms, oil fields, electromechanical installation and maintenance, and industrial enterprises that use electricity as industrial power or energy. It is suitable for measuring the resistance value of various insulating materials and the insulation resistance of transformers, motors, cables and electrical equipment.
MTS-10-10K Insulation resistance meter consists of medium and large scale integrated circuits. The output power of the watch is large, and the output voltage level is a lot (with 6 voltage levels). Rated insulation test voltage range 250V ~ 10kV, insulation resistance measurement range 0.01MΩ ~ 2000GΩ. DC voltage measurement range 0 ~ 1000V, AC voltage measurement range 0 ~ 750V.
MTS-10-10K TECHNICAL PARAMETERS
Test Function | Insulation resistance test, voltage test | |
Condition | 23°C±5°C,below 75%rh | |
Rated Voltage (V) | 250, 500, 1000, 2500V, 5000V, 10000V | |
Measuring Voltage(V) | Rated voltage×(1±10%) | |
Insulation Resistance Range(GΩ) | 0.01MΩ~2000GΩ Precision ±3%rdg±5dgt | |
Insulation Resistance Resolution | 0.01MΩ | |
DC voltage range | 0~1000V Resolution 0.1V | |
AC voltage range 0~750V | Resolution 0.1V | |
Output short circuit current | ≥5mA(10000V) | |
Absorption Ratio and Polarization Index Measurement | Have | |
Power Supply | 12V rechargeable battery | |
Backlight | Controllable gray screen backlight, suitable for use in dim places | |
Display mode | 4-bit large LCD display, gray screen backlight | |
LCD display size | 108mm×65mm | |
Instrument size | 227.2mm (L)×227.5mm (W)×153mm (H) | |
USB interface | With USB interface, software monitoring, storage data can be uploaded to the computer, save the print | |
Communication Line | USB communication line 1PC | |
Test Line | High voltage robs red 3meter, high voltage test line black 1.5meter, green 1.5meter | |
Data Storage | 500 groups, “FULL” symbol indicates that storage is full | |
Data Review | Data review function: “READ” symbol display | |
Overflow Display | Exceed measurement range overflow function: “OL” symbol display | |
Alarm Function | Alarm when the measured value exceeds the alarm setting value | |
Power Consumption | Standby: 30mA Max (backlight off) | |
Turn on backlight: 42mA Max | ||
Measure:300mA Max (backlight off) | ||
Instrument weight | 2720g (including battery) | |
Battery voltage | When the battery voltage is low, low battery symbol “ ” will display | |
Automatic shut-down | automatic shutdown after 15 minutes boot | |
Insulation Resistance | ≥50MΩ (between Measuring line and shell) | |
Pressure Resistance | AC3kV/50Hz 1min | |
Working Temperature and Humidity | -10℃~+50℃<85%RH | |
Storage Temperature and Humidity | -15℃~+55℃<90%RH | |
Suitable for Safety Regulations | IEC61010-1, IEC1010-2-31, IEC61557-1,5, IEC60529(IP54), Pollution grade 2, CAT III 300V |
GENERAL INFORMATION
What is Insulation Test?
Insulation resistance measurement is a test performed at the production stage and service stage for almost every electrical product and device. As a result of these tests, malfunctions that may threaten life safety are detected and prevented. We can make this determination safely and accurately thanks to Insulation Testers.
What is Insulation Tester?
Insulation Testers are test devices that measure insulation resistance. Insulation must be provided between the parts with voltage in the working environment and parts without voltage. If this condition is not met, there will be electricity in places where electrical energy should not be available and it will pose a danger to life safety. In addition, insulation should be provided between the sections inside the devices. This is very important for the devices to give healthy, accurate and reliable results.
Where are Insulation Testers Used?
- In power and distribution transformers
- Insulation tests of engines and generators
- Periodic tests and maintenance tests on production lines
- It can perform tests for analysis and fault detection of all kinds of insulation problems.
Why are Insulation Testers Important?
Insulation testers are one of the most important assistants of an engineer. You can get very fast results and take action very quickly. In addition, it is very dangerous for a person to do such tests without using a device. In other words, it is a very important device in terms of life safety. In addition, you can make your future plans more comfortably with periodic maintenance. If we talk about the importance of the device;
- One of its most important advantages is that it can be used in many areas.
- With many different step settings, you can choose the appropriate level very easily.
- It allows the measurement of very high insulation resistance values.
- There are automatic discharge systems after each test.
- The data can be analyzed with special software prepared for the computer.
- It provides the opportunity to follow the measurements live.
Reviews