This system is specially designed and manufactured for the power transformer production or maintenance department to do the frequency doubling induction withstand voltage test power supply. The continuous operation time is allowed not to exceed 4 hours. The output frequency is 150Hz, and the maximum load transformer capacity is 3150kVA. An intermediate transformer is required when the voltage on the low-voltage side of the transformer exceeds 400V.
TECHNICAL PARAMETERS
GENERATOR MOTOR SET | |
Rated Capacity | 30kVA |
Supply Input Voltage | 380V |
Supply Input Frequency | 50Hz |
Generator Input Current | Motor running current 14A, exciting current 18A |
Rated Speed | 1480r / min |
Exciting Voltage | 185V |
Exciting Current | 18A |
Excitation Frequency | 50Hz |
Output Voltage | 20~800V |
Output Current | 15A |
Output Frequency | 150Hz |
DVDF CONTROL CONSOLE | |
Power Source | 3 phase |
Rated Capacity | 30kVA |
System Input Voltage | 0.38kV |
System Output Voltage | 20-800V |
Exciting Voltage | 0-180V |
Exciting Current | 22A |
Frequency | 150 Hz |