ANFS(F) series AC power supply adopts FPGA digital control, instantaneous waveform control and high-frequency pulse width modulation (SPWM) technologies. It has the advantages of fast response speed, high output accuracy, and superior waveform quality.
The ANFS(F) series AC power supply adopts FPGA digital control, instantaneous waveform control and high-frequency pulse width modulation (SPWM) technologies. It has the advantages of fast response speed, high output accuracy, and superior waveform quality; it can withstand 3 times the rated current impact , a variety of output modes, which can achieve “one machine with multiple functions” to meet the needs of customers for flexible use; it adopts 8-inch color LCD with exquisite and high-grade appearance, and digital keys make the operation more convenient. Mainly used in applications such as home appliances, motors and production lines. It is one solution that meets the basic needs of traditional industries and a power supply alternative for equipment upgrades. It also provides laboratories, quality inspection units, scientific research institutes and other applications more flexible power configuration scheme.
TECHNICAL PARAMETERS
Model | ANFS015A(F) | ANFS030A(F) | ANFS045A(F) | ANFS060A(F) | ANFS090A(F) | ANFS120A(F) | ANFS180A(F) | ANFS240A(F) | ||
Capacity | 15kVA | 30kVA | 45kVA | 60kVA | 90kVA | 120kVA | 180kVA | 240kVA | ||
Input | Voltage,Frequency | 3-phase 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz | ||||||||
AC Output | Mode | 3 phase standard mode,3 phase independent mode,parallel single phase mode | ||||||||
Voltage | Phase voltage: 0.0 〜 300.0V,Automatic files: (low) 0.0 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:0.0 〜 300.0V | |||||||||
Frequency | 45.00~240.00Hz | |||||||||
3 phase standard mode | 110V | 45.4A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | 545.4A | 727.2A | |
220V | 22.7A | 45.4A | 68.2A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | ||
3 phase independent mode | 110V | 45.4A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | 545.4A | 727.2A | |
220V | 22.7A | 45.4A | 68.2A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | ||
Parallel single phase mode | 110V | 136.3A | 272.7A | 409.1A | 545.4A | 818.2A | 1090.9A | 1636.4A | 2181.8A | |
220V | 68.2A | 136.3A | 204.5A | 272.7A | 409.1A | 545.4A | 818.2A | 1090.9A | ||
Setting Accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value+0.2%×full scale value | ||||||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | |||||||||
Testing Accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value+0.2%×full scale value | ||||||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | |||||||||
Current | Resolution:0.1A/1A,accuracy:0.3%×reading value +0.3%×full scale value | |||||||||
Power | Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value+0.45%×full scale value | |||||||||
Frequency Stability | ≤0.02% | |||||||||
Voltage Distortion | Linear load:THD<1% | |||||||||
Transient recovery time | 20ms | |||||||||
Three phase phase difference | Three phase standard mode:120°±2° | |||||||||
Crest factor | 1.41±0.1 | |||||||||
Source voltage effect | ≤1% | |||||||||
Load Effect | ≤1% | |||||||||
Over Power | 105%<output≤110% the output will be stopped within 15s ;110%<output≤200% the output will be stopped within 5s; 200%<output≤300% the output will be stopped within 2s ;300%<output the output will be stopped immediately。 | |||||||||
Protection Input Mode | IGBT overheat、 IGBT over current、 Transformer overheat、lack voltage、 Input over voltage、 Output lack voltage、Output over voltage、 Output over load、 Output short cirluit、output over current | |||||||||
Function | Display mode;Start | 8 inch LCD display,resolution:800*600;Soft-start time:0.0~99.9s | ||||||||
Online adjustment function | In the normal mode, the output voltage and frequency can be adjusted online | |||||||||
Memory function | Power down memory function, memory last output mode and parameters; shortcut group:10 groups | |||||||||
Line voltage crop compensation | 0.000~0.500Ω | |||||||||
Communication | Standard:RS232;Optional:RS485、GPIB、Ethernet、Analog control port | |||||||||
Environment | Temperature and humidity | 0~40℃;20~90%RH | ||||||||
Dimension W×H×D(mm) | 600×1130×1018 | 700×1330×1218 | 800×1768×1418 | |||||||
Weight(kg) | 280 | 330 | 470 | 590 | 780 | 1030 | 1320 | 1490 |
Model | ANFS350A | ANFS450A | ANFS550A | ANFS650A | ||
Capacity | 350kVA | 450kVA | 550kVA | 650kVA | ||
Input | Voltage, Frequency | 3-phase 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz | ||||
AC Output | Mode | 3 phase standard mode,3 phase independent mode | ||||
Voltage | Automatic files: (low) 0.0 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:0.0 〜 300.0V | |||||
Frequency | 45.00~240.00Hz | |||||
3 phase standard mode | 110V | 1060A | 1363A | 1666A | 1970A | |
220V | 530.3A | 681.8A | 833.3A | 984.8A | ||
3 phase independent mode | 110V | 1060A | 1363A | 1666A | 1970A | |
220V | 530.3A | 681.8A | 833.3A | 984.8A | ||
Setting accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value | ||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | |||||
Testing accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value | ||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | |||||
Current | Resolution:0.1A/1A,accuracy:0.3%×reading value +0.3%×full scale value | |||||
Power | Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value +0.45%×full scale value | |||||
Frequency stability | ≤0.02% | |||||
Voltage distortion | Linear load:THD<3% | |||||
Transient recovery time | 20ms | |||||
Three phase phase difference | Three phase standard mode:120°±2° | |||||
Crest factor | 1.41±0.1 | |||||
Source voltage effect | ≤1% | |||||
Load effect | ≤1% | |||||
Over Power | 105%<output≤110% the output will be stopped within 15s ;110%<output≤200% the output will be stopped within 5s; 200%<output≤300% the output will be stopped within 2s ;300%<output the output will be stopped immediately. | |||||
Protection Input mode | IGBT overheat、 IGBT over current、 Transformer overheat、lack voltage、 Input over voltage、 Output lack voltage、Output over voltage、 Output over load、 Output short cirluit、output over current | |||||
Function | Display mode;Start | 8 inch LCD display,resolution:800*600;Soft-start time:0.0~99.9s | ||||
Online adjustment function | In the normal mode, the output voltage and frequency can be adjusted online | |||||
Memory function | Power down memory function, memory last output mode and parameters; shortcut group:10 groups | |||||
Line voltage crop compensation | 0.000~0.500Ω | |||||
Communication | Standard:RS232;Optional:RS485、GPIB、Ethernet、Analog control port | |||||
Environment | Temperature and Humidity | 0~40℃;20~90%RH | ||||
Dimension W×H×D(mm) | 1800×2000×1400 | 2400×2000×1400 | 4800(1200×4)×2000×1200 | |||
Weight (Kkg) | 2730 | 3150 | 4270 | 4660 |