ANFP(F) series programmable AC power supply adopts FPGA digital control, instantaneous waveform control and SPWM technologies. It has the advantages of fast response speed, high output accuracy and superior waveform quality.
The ANFP(F) series programmable AC power supply adopts FPGA digital control, instantaneous waveform control and high-frequency pulse width modulation (SPWM) technologies. It has the advantages of fast response speed, high output accuracy, and superior waveform quality; it can withstand 3 times the rating Current impact capability, strong load adaptability; with multiple output modes and complex programmable functions, which can achieve test requirements such as ladder, step, gradual change, etc.; with three-phase unbalanced output mode, to achieve relevant regulatory tests or simulate special power grids And so on. It can be widely used in laboratories, quality inspection units, scientific research institutes and certification centers.
TECHNICAL PARAMETERS
Model | ANFP015A(F) | ANFP030A(F) | ANFP045A(F) | ANFP060A(F) | ANFP090A(F) | ANFP120A(F) | ANFP180A(F) | ANFP240A(F) | ||
Capacity | 15kVA | 30kVA | 45kVA | 60kVA | 90kVA | 120kVA | 180kVA | 240kVA | ||
Input | Voltage,Frequency | 3-phase 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz | ||||||||
AC Output | Model | 3 phase standard mode, 3 phase unbalanced mode, 3 phase independent mode, parallel single phase mode | ||||||||
Voltage | Phase voltage: 0.0 〜 300.0V,Automatic files: (low) 0.0 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:0.0 〜 300.0V | |||||||||
Frequency | 45.00~240.00Hz | |||||||||
3 phase standard /3 phase unbalanced mode rated current | 110V | 45.4A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | 545.4A | 727.2A | |
220V | 22.7A | 45.4A | 68.2A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | ||
3 phase independent mode rated current | 110V | 45.4A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | 545.4A | 727.2A | |
220V | 22.7A | 45.4A | 68.2A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | ||
Parallel single-phase mode rated current | 110V | 136.3A | 272.7A | 409.1A | 545.4A | 818.2A | 1090.9A | 1636.4A | 2181.8A | |
220V | 68.2A | 136.3A | 204.5A | 272.7A | 409.1A | 545.4A | 818.2A | 1090.9A | ||
Setting accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value+0.2%×full scale value | ||||||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | |||||||||
Testing accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value+0.2%×full scale value | ||||||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | |||||||||
Current | Resolution:0.1A/1A,accuracy:0.3%×reading value+0.3%×full scale value | |||||||||
Power | Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value+0.45%×full scale value | |||||||||
Voltage distortion | Linear load:THD<1% | |||||||||
Transient recovery time | 20ms | |||||||||
3 phase phase difference | 3 phase standard mode:120°±2° | |||||||||
3 phase unbalanced mode:0.0°~359.9°,0.1°adjustable | ||||||||||
Crest factor | 1.41±0.1 | |||||||||
Source voltage effect | ≤1% | |||||||||
Load effect | ≤1% | |||||||||
Over power | 105%<Output≤110% the output will be stopped within 15 Sec ;110%<Output≤200% the output will be stopped within 5 Sec 200%<Output≤300% the output will be stopped within 2 Sec ;300%<Output the output will be stopped immediately |
|||||||||
Protection mode | IGBT overheat、 IGBT over current、 Transformer overheat、lack voltage、 Input over voltage、 Output lack voltage、Output over voltage、 Output over load、 Output short cirluit、output over current | |||||||||
Function | Display mode | 8 inch LCD display, resolution: 800*600;Soft-start:0.0~99.9s | ||||||||
Output waveform | Sine wave, harmonic (superposition 2~40 second harmonic) | |||||||||
Programming function | Step mode | 9999 step | ||||||||
Stage mode | 100 stage 999999 cycle | |||||||||
Varations mode | 100 stage999999 cycle | |||||||||
Online adjustment function | Under normal mode, the output voltage and output frequency can be adjusted online, which can be switched on line. | |||||||||
Memory function/ Shortcut group | Power down memory function, memory last output mode and parameters; 10 groups | |||||||||
Line voltage crop compensation | 0.000~0.500Ω | |||||||||
Communication | RS232(standard), RS485(options)GPIB(options), Ethernet(options), Analog control port(options) | |||||||||
Environment | Temperature/Humidity | 0~40℃;20~90%RH | ||||||||
Dimension W×H×D(mm) | 1000×1990×800 | 1200×1990×800 | 1200×1990×1000 | |||||||
Weight (kg) | 310 | 360 | 500 | 620 | 810 | 1060 | 1280 | 1380 |
Model | ANFP350A(F) | ANFP450A(F) | ANFP550A(F) | ANFP650A(F) | |||
Capacity | 350kVA | 450kVA | 550kVA | 650kVA | |||
Input | Voltage,Frequency | 3-phase 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz | |||||
AC Output | Mode | 3 phase standard mode, 3 phase unbalanced mode, 3 phase independent mode | |||||
Voltage | Phase voltage: 0.0 〜 300.0V,Automatic files: (low) 0.0 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:0.0 〜 300.0V | ||||||
Frequency | 45.00~240.00Hz | ||||||
3 phase standard /3 phase unbalanced mode rated current | 110V | 1060A | 1363A | 1666A | 1970A | ||
220V | 530.3A | 681.8A | 833.3A | 984.8A | |||
3 phase independent mode | 110V | 1060A | 1363A | 1666A | 1970A | ||
220V | 530.3A | 681.8A | 833.3A | 984.8A | |||
Setting Accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value | |||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | ||||||
Testing Accuracy | Voltage | Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value | |||||
Frequency | Resolution:0.01Hz,accuracy:0.05% | ||||||
Current | Resolution:0.1A/1A,accuracy:0.3%×reading value +0.3%×full scale value | ||||||
Power | Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value+0.45%×full scale value | ||||||
Voltage distortion | Linear load:THD<3% | ||||||
Transient recovery time | 20ms | ||||||
3 phase phase difference | 3 phase standard mode:120°±2° | ||||||
3 phase unbalanced mode:0.0°~359.9°,0.1°adjustable | |||||||
Crest factor | 1.41±0.1 | ||||||
Source voltage effect | ≤1% | ||||||
Load effect | ≤1% | ||||||
Over power | 105%<Output≤110% the output will be stopped within 15s ;110%<Output≤200% the output will be stopped within 5s;
200%<Output≤300% the output will be stopped within 2s ;300%<Output the output will be stopped immediately |
||||||
Protection mode | IGBT overhea, IGBT over curren, Transformer overheat, Input lack voltag, Input over voltag, Output lack voltag, Output over voltag, Lack output phase, Output over load, Output short circuit, Output over current | ||||||
Function | Display mode | 8 inch LCD display, resolution: 800*600 | |||||
Programming function | Step mode | 9999 set | |||||
Stage mode | 100 stage 999999 cycle | ||||||
Varations mode | 100 stage999999 cycle | ||||||
Online adjustment function | Under normal mode, the output voltage and output frequency can be adjusted online, which can be switched on line. | ||||||
Memory function/ Shortcut group | Power down memory function, memory last output mode and parameters;10 groups | ||||||
Line voltage crop compensation | 0.000~0.500Ω | ||||||
Communication | RS232(standard), RS485(options), GPIB(options), Ethernet(options), Analog control port(options) | ||||||
Environment | Temperature/Humidity | 0~40℃;20~90%RH | |||||
Dimension W×H×D(mm) | 1800×2000×1400 | 2400×2000×1400 | 4800(1200×4)×2000×1200 | ||||
Weight (kg) | 2730 | 3150 | 4270 | 4660 |