The parallel aviation ground power system consists of tow(or more) parallel aviation ground power units of same power capacity via systematic planning and development, so as to achieve parallel operation. This system is mainly used in airports, hangars and other occasions, to provide external 400HZ power for production inspection, repair and maintenance of civil and military aircraft. In addition, the quantity of running power unites are adjusted automatically in real time based on the load capacity, to achieve intelligent management of parallel operation and energy-saving.
Main Features:
★400Hz Intermediate Frequency Power Supply or 28.5V DC Power
★Outdoor Version,IP55 of Protection level
★Far-end Voltage Drop Compensation Funtion
★High Reliability and Convenient & Swift Maintenance
★Aircrafts Inter lock power Supply Function
★Operation Environment Temperature:-25℃~45℃
★Communication Interface:RS232/485
*This list is for general reference only and may not be entirely acurate for all aircraft. Please confirm all equipment meets the requirements of your aircraft with the owners/maintenance manuals prior to purchasing or using with your aircraft.
Stationary Indoor Type
Capacity | AN 170 60R | AN 170 90R | AN 171 20R | AN 171 50R | AN 171 80R |
Output Capacity | 60kVA | 90kVA | 120kVA | 150kVA | 180kVA |
Rated Current Output | 174A | 261A | 348A | 435A | 522A |
Dimension | 1650 * 600 * 1100 | 2000 * 900 * 1700 |
Stationary Outdoor Type
Capacity | AN 170 60F | AN 170 90F | AN 171 20F | AN 171 50F | AN 171 80F |
Output Capacity | 60kVA | 90kVA | 120kVA | 150kVA | 180kVA |
Rated Current Output | 174A | 261A | 348A | 435A | 522A |
Dimension | 1650 * 600* 1100 | 2000 * 900 * 1700 |
Trailer
Capacity | AN 170 60T | AN 170 90T | AN 171 20T | AN 171 50T | AN 171 80T |
Output Capacity | 60kVA | 90kVA | 120kVA | 150kVA | 180kVA |
Rated Current Output | 174A | 261A | 348A | 435A | 522A |
Dimension | 1650 *600 * 1100 without trailer dimension | 2000 *900 *1700 without trailer dimension |
Bridge Type
Capacity | AN 170 60B | AN 170 90B | AN 171 20B | AN 171 50B | AN 171 80B | |||||
Output Capacity | 60 kVA | 90 kVA | 120 kVA | 150 kVA | 180 kVA | |||||
Rated Current Output | 174A | 261A | 348A | 435A | 522A | |||||
Dimension | 1650*600*1100 | 2000*900*1700 | ||||||||
Capacity | Stati onary In door Type | Stationary Outdoor Type | Trailer | Bridge Type | ||||||
AC Input | Input Volt age | 380V±40V 3-phase 3-line Input | ||||||||
Input Fre quency | 50Hz±5Hz | |||||||||
AC Charac teristics | Out put Volt age | Rated Output Voltage:115V Adjustable Output Voltage:100V~130V | ||||||||
Out put Fre quency | 400Hz±0.4Hz | |||||||||
Insta neous Chanac teristics | Meet with MH/T 6018-1999 Requirement | |||||||||
THD | ≤3% | |||||||||
Crest Factor | 1.41±0.10 | |||||||||
Single Harmonic Value | ≤3% | |||||||||
Voltage Modulation Range | ≤2.5% | |||||||||
Display | Volt age | (highest) Resolution 0.1V MFE (Max. Permissible Error): ±1V | ||||||||
Cur rent | (highest) Resolution 0.1A MFE (Max. Permissible Error): ±2.5% | |||||||||
Efficiency | ≥85% |